12 AWG 4C Type MC-HL W/G Corrugated Welded Armor XLPE/PVC Jacket Control Cable 600V
Application:
Southwire’s 600 Volt Type MC-HL ARMOR-X control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, 250°C for short circuit conditions, and -40°C for cold bend. For uses in Class I, II, and III, Division 1 and 2 hazardous locations per NEC Article 501, 502, and 503.
Also known as:
12 AWG 4C Metal Clad (MC) Cable Control Cable with Corrugated Steel 12 AWG 4C Armor Welded Armor MC Cable 12 AWG 4C MC-HL (Heat and Light Resistant) Cable 12 AWG 4C XLPE Insulated Control Cable PVC Jacketed Control Cable 600V Rated Control Cable 12 AWG 4C MC-HL Cable with Ground Corrugated Armor MC Cable
Construction:
Conductor:
7 strands class B compressed copper per ASTM B3 and B8
Insulation:
Cross Linked Polyethylene (XLPE) XHHW-2
Grounding Conductor:
Class B compressed stranded copper with green insulation
Filler:
Polypropylene filler as needed
Binder:
Polyester flat thread binder tape as needed
Armor:
ARMOR-X Continuous Corrugated Aluminum Welded Armor
Overall Jacket:
Polyvinyl Chloride (PVC) Jacket
Standards:
• ASTM B3 Soft or Annealed Copper Wire
• ASTM B8 Concentric-Lay-Stranded Copper Conductors
• UL 44 Thermoset-Insulated Wires and Cables
• UL 1569 Metal-Clad Cables
• UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
• UL 2225 Cables and Cable-Fittings For Use In Hazardous (Classified) Locations
• ICEA S-58-679 Control Cable Conductor Identification Method 1 Table 2
• ICEA S-73-532 Standard for Control, Thermocouple Extension and Instrumentation Cables
• ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
• IEEE 1202 FT4 Vertical Tray Flame Test (70,000 Btu/hr) and ICEA T-29-520 – (210,000 Btu/hr)
Specifications:
• Size: 12
• Number of Conductor: 4
• Number of Strands: 7
• Insulation Thickness (Mil): 30
• Ground No. x AWG: 1 x 12
• Diameter Over Armor(inch): 0.650
• Jacket Thickness (mil):50
• Approx. OD (In): 0.756
• Copper Weight lb/1000ft: 102
• Approx. Weight (Lbs/1000’Ft): 272
• DC Resistance @ 25°C Ω /1000ft: 1.662
• AC Resistance @ 75°Ω /1000ft: 2.002
• Allowable Ampacity At 75°C (Amp): 20
• Allowable Ampacity At 90°C (Amp): 24
|