1 AWG HVTECK Copper Triplex Cable: NLEPR Insulated, 25kV, 133% IL, Red PVC Jacket (CSA Certified)

$19.90

In stock

Quantity
SKU: NNC581881 Category: Brand:

Description

[pdf]  [/pdf]

1 AWG 3C HVTECK Copper 320 mil NLEPR TS AIA 25kV 133% IL Red PVC Jacket CSA

Application:

The 25kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.

Also Known As:

1 AWG 3C HVTECK Copper 3/C 320 mil cable, NLEPR TS AIA 25kV cable, 320 mil copper cable 25kV, CSA 25kV cable, 3 conductor 25kV cable, 1 AWG 3C HVTECK NLEPR TS AIA cable, 133% insulation 25kV cable, 320 mil PVC jacketed wire, 1 AWG 3C HVTECK CSA cable 25kV, 3/C 25kV copper wire.

Construction:

• Conductor: Class B compressed stranded bare copper per ASTM B3 and ASTM B8
• Conductor Shield: 
Semi-conducting cross-linked copolymer
• Insulation: 
320 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 133% insulation level
• Insulation Shield: 
Strippable semi-conducting cross-linked copolymer
• Copper Tape Shield: 
Helically wrapped 5 mil copper tape with 25% overlap
• Filler: 
Interstices filled with non-hydroscoping/non-wicking fillers
• Grounding Conductor: 
Class B compressed stranded bare copper ground per ASTM B3 and ASTM B8
• Binder: 
Polypropylene tape
• Inner Jacket: 
PVC inner jacket
• Armour: 
Aluminum Interlocked Armour (AIA)
• Overall Jacket: 
Red Polyvinyl Chloride (PVC) Jacket

Standards:

• ASTM B3 Soft or Annealed Copper Wire
• ASTM B8 Concentric-Lay-Stranded Copper Conductors
• CSA C22.2 No. 174 Cables in Hazardous Locations
• CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
• CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications – 5 to 46 KV
• CSA C68.3 Shielded & Concentric Neutral Power Cable – 5 to 46 kV
• CSA LTGG [-40°C] – as per C68.10 – for Cold Bend and Impact rating
• CSA HL – for Hazardous Locations rating
• CSA SUN RES – for Sunlight Resistant rating
• ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
• ICEA T-29-520 Flame Test (210,000 BTU/Hr)
• IEEE 383 Flame Test (70,000 btu)
• IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
• FT1 Flame Test (1,706 BTU/Hr nominal – Vertical Wire Flame Test)
• AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)

Specifications:

• Size: 1 AWG
• Number of conductor: 3
• Number of Strands: 19
• Diameter Over Conductor (inch):   0.322
• Diameter Over Insulation (inch):  1.000
• Insul. Thickness mil: 320
• Diameter Over Insulation Shield (inch):  1.060
• Ground Size AWG: 6
• Inner Jacket Thickness (mil):  110 
• Diameter Over Armor (inch):  2.903
• Overall Jacket Thickness mil :   75
• Approx. OD inch :  3.053
• Copper Weight lb/1000ft:  1173
• Approx. Weight (Lbs/1000’Ft): 4124
• Min Bending Radius (In):  21.4
• DC Resistance @ 25°C Ω /1000ft:  0.128
• AC Resistance @ 90°Ω /1000ft:  0.162
• Inductive Reactance @ 60HzΩ/1000ft:  0.050
• Allowable Ampacity In Air 90°C Amp:  202
• Allowable Ampacity Directly Buried 90°C Amp:  226

Compatible with Manufacturer

Southwire 581881^